INDEPENDENT CRITICAL-POWER DIRECTORY Public sources. Clear decisions.
Delta / SOURCE RECORD 2354255

DPH-105K-LV

○ ENERGY STAR feedRetrieved 2026-09-12
THE CONFIGURATION BEHIND THESE RATINGS

Minimum tested model: DPH-105K-LV

The source identifies this model as the minimum tested configuration. The output ratings and load-specific efficiency values below apply to that configuration.

Efficiency test mode (lowest input dependency)
Voltage and Frequency Independent
Test input voltage
120 V
Test input frequency
60 Hz
Test output voltage
120 V
Test output frequency
60 Hz
15 kWMinimum tested active output
15 kVAMinimum tested apparent output
YesModular

These are source-reported minimum configuration ratings, not the maximum capacity of the model family. Test voltages above describe the efficiency test; reported voltage ranges below are separate source fields.

Inside the specification

SOURCE-REPORTED
Brand
Delta
Catalog model identifier
DPH-105K-LV
Reported input voltage
120-127 V
Reported output voltage
120-127 V
Reported input frequency
50-60 Hz
Topology
Multi-Mode Double Conversion
Modular design
Yes
Rack mountable
No
Application
Data Center,Commercial
Reported markets
United States, Canada
Certification date
2020-01-20

Efficiency at a glance

Summary value reported by the source: 95.6%. Compare the tested model, voltage and mode above before interpreting differences.

25% of minimum tested output94.5%
50% of minimum tested output95%
75% of minimum tested output94.6%
100% of minimum tested output93.9%

Load-specific values: minimum configuration, lowest-input-dependency test mode. Unreported values remain blank in exports.

CONTINUE YOUR RESEARCH

Nearby tested output. Different details.

Within 25% of this minimum tested output rating. These are research candidates, not approved substitutes.

Delta
RT-15K3P ↗

Source record 2340463

15kW

Minimum tested active output

Reported input voltage220-240 VModularNo
○ ENERGY STAR feed
Liebert
GXT5-15KMVRT11UXLN ↗

Source record 2354251

15kW

Minimum tested active output

Reported input voltage100-125 VModularNo
○ ENERGY STAR feed
Vertiv
GXT5-15KMVRT11UXLN ↗

Source record 2354252

15kW

Minimum tested active output

Reported input voltage100-125 VModularNo
○ ENERGY STAR feed