INDEPENDENT CRITICAL-POWER DIRECTORY Public sources. Clear decisions.
EATON / SOURCE RECORD 4577046

S3M50K

○ ENERGY STAR feedRetrieved 2026-09-12
THE CONFIGURATION BEHIND THESE RATINGS

Minimum tested model: S3M50K

The source identifies this model as the minimum tested configuration. The output ratings and load-specific efficiency values below apply to that configuration.

Efficiency test mode (lowest input dependency)
Voltage and Frequency Independent
Test input voltage
220 V
Test input frequency
50 Hz
Test output voltage
220 V
Test output frequency
50 Hz
50 kWMinimum tested active output
50 kVAMinimum tested apparent output
NoModular

These are source-reported minimum configuration ratings, not the maximum capacity of the model family. Test voltages above describe the efficiency test; reported voltage ranges below are separate source fields.

Inside the specification

SOURCE-REPORTED
Brand
EATON
Catalog model identifier
S3M50K
Reported input voltage
208-220 V
Reported output voltage
208-220 V
Reported input frequency
50-60 Hz
Topology
Double Conversion
Modular design
No
Rack mountable
No
Application
Data Center,Consumer,Commercial
Reported markets
United States
Certification date
2026-01-27

Efficiency at a glance

Summary value reported by the source: 95.5%. Compare the tested model, voltage and mode above before interpreting differences.

25% of minimum tested output95.8%
50% of minimum tested output95.9%
75% of minimum tested output94.5%
100% of minimum tested output93.3%

Load-specific values: minimum configuration, lowest-input-dependency test mode. Unreported values remain blank in exports.

CONTINUE YOUR RESEARCH

Nearby tested output. Different details.

Within 25% of this minimum tested output rating. These are research candidates, not approved substitutes.

Liebert
51SA050BAA ↗

Source record 2335462

50kW

Minimum tested active output

Reported input voltage480-480 VModularYes
○ ENERGY STAR feed
Vertiv
51SA050BAA ↗

Source record 2335463

50kW

Minimum tested active output

Reported input voltage480-480 VModularYes
○ ENERGY STAR feed
Schneider Electric
GVSUPS50KR0B5GS ↗

Source record 2355668

50kW

Minimum tested active output

Reported input voltage480-480 VModularNo