INDEPENDENT CRITICAL-POWER DIRECTORY Public sources. Clear decisions.
Liebert / SOURCE RECORD 2335122

47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]

○ ENERGY STAR feedRetrieved 2026-09-12
THE CONFIGURATION BEHIND THESE RATINGS

Minimum tested model: 47SA010A0C00

The catalog model is 47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]; the source identifies 47SA010A0C00 as its minimum tested model. The output ratings and load-specific efficiency values below belong to that tested configuration.

Efficiency test mode (lowest input dependency)
Voltage and Frequency Independent
Test input voltage
208 V
Test input frequency
60 Hz
Test output voltage
208 V
Test output frequency
60 Hz
10 kWMinimum tested active output
10 kVAMinimum tested apparent output
YesModular

These are source-reported minimum configuration ratings, not the maximum capacity of the model family. Test voltages above describe the efficiency test; reported voltage ranges below are separate source fields.

Inside the specification

SOURCE-REPORTED
Brand
Liebert
Catalog model identifier
47SA040A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]
Reported input voltage
176-253 V
Reported output voltage
198-231 V
Reported input frequency
40-70 Hz
Topology
Multi-Mode Double Conversion
Modular design
Yes
Rack mountable
No
Application
Commercial,Consumer,Data Center
Reported markets
United States, Taiwan, Japan, Canada
Certification date
2019-01-23

Efficiency at a glance

Summary value reported by the source: 94.2%. Compare the tested model, voltage and mode above before interpreting differences.

25% of minimum tested output89.3%
50% of minimum tested output93.2%
75% of minimum tested output94.5%
100% of minimum tested output94.9%

Load-specific values: minimum configuration, lowest-input-dependency test mode. Unreported values remain blank in exports.

CONTINUE YOUR RESEARCH

Nearby tested output. Different details.

Within 25% of this minimum tested output rating. These are research candidates, not approved substitutes.

Delta
RT-10K ↗

Source record 2327102

10kW

Minimum tested active output

Reported input voltage200-240 VModularNo
○ ENERGY STAR feed
Liebert
GXT5-10KIRT5UXLN ↗

Source record 2328744

10kW

Minimum tested active output

Reported input voltage200-240 VModularNo
○ ENERGY STAR feed
Vertiv
GXT5-10KIRT5UXLN ↗

Source record 2328745

10kW

Minimum tested active output

Reported input voltage200-240 VModularNo
○ ENERGY STAR feed