INDEPENDENT CRITICAL-POWER DIRECTORY Public sources. Clear decisions.
Liebert / SOURCE RECORD 2335388

47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]

○ ENERGY STAR feedRetrieved 2026-09-12
THE CONFIGURATION BEHIND THESE RATINGS

Minimum tested model: 47SA120A0C00

The catalog model is 47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]; the source identifies 47SA120A0C00 as its minimum tested model. The output ratings and load-specific efficiency values below belong to that tested configuration.

Efficiency test mode (lowest input dependency)
Voltage and Frequency Independent
Test input voltage
208 V
Test input frequency
60 Hz
Test output voltage
208 V
Test output frequency
60 Hz
120 kWMinimum tested active output
120 kVAMinimum tested apparent output
YesModular

These are source-reported minimum configuration ratings, not the maximum capacity of the model family. Test voltages above describe the efficiency test; reported voltage ranges below are separate source fields.

Inside the specification

SOURCE-REPORTED
Brand
Liebert
Catalog model identifier
47SA120A[0|1|2|3][C|Y][0|F|H|M|G|L][0|1]
Reported input voltage
208-220 V
Reported output voltage
208-220 V
Reported input frequency
50-60 Hz
Topology
Multi-Mode Double Conversion
Modular design
Yes
Rack mountable
No
Application
Commercial,Consumer,Data Center
Reported markets
United States, Taiwan, Japan, Canada
Certification date
2019-01-23

Efficiency at a glance

Summary value reported by the source: 95.6%. Compare the tested model, voltage and mode above before interpreting differences.

25% of minimum tested output93.9%
50% of minimum tested output95.3%
75% of minimum tested output95.2%
100% of minimum tested output94.7%

Load-specific values: minimum configuration, lowest-input-dependency test mode. Unreported values remain blank in exports.

CONTINUE YOUR RESEARCH

Nearby tested output. Different details.

Within 25% of this minimum tested output rating. These are research candidates, not approved substitutes.

Liebert
eXM 0120kTK16FN01000 ↗

Source record 2336437

120kW

Minimum tested active output

Reported input voltage228-478 VModularNo
○ ENERGY STAR feed
Vertiv
eXM 0120kTK16FN01000 ↗

Source record 2336438

120kW

Minimum tested active output

Reported input voltage228-478 VModularNo
○ ENERGY STAR feed