INDEPENDENT CRITICAL-POWER DIRECTORY Public sources. Clear decisions.
Liebert / SOURCE RECORD 2335946

51SA160AQA

○ ENERGY STAR feedRetrieved 2026-09-12
THE CONFIGURATION BEHIND THESE RATINGS

Minimum tested model: 51SA160AQA

The source identifies this model as the minimum tested configuration. The output ratings and load-specific efficiency values below apply to that configuration.

Efficiency test mode (lowest input dependency)
Voltage and Frequency Independent
Test input voltage
480 V
Test input frequency
60 Hz
Test output voltage
480 V
Test output frequency
60 Hz
40 kWMinimum tested active output
40 kVAMinimum tested apparent output
YesModular

These are source-reported minimum configuration ratings, not the maximum capacity of the model family. Test voltages above describe the efficiency test; reported voltage ranges below are separate source fields.

Inside the specification

SOURCE-REPORTED
Brand
Liebert
Catalog model identifier
51SA160AQA
Reported input voltage
480-480 V
Reported output voltage
480-480 V
Reported input frequency
60-60 Hz
Topology
Multi-Mode Double Conversion
Modular design
Yes
Rack mountable
No
Application
Commercial,Consumer,Data Center
Reported markets
United States, Taiwan, Japan, Canada
Certification date
2019-01-23

Efficiency at a glance

Summary value reported by the source: 95.5%. Compare the tested model, voltage and mode above before interpreting differences.

25% of minimum tested output94.3%
50% of minimum tested output95.8%
75% of minimum tested output96.2%
100% of minimum tested output96.1%

Load-specific values: minimum configuration, lowest-input-dependency test mode. Unreported values remain blank in exports.

CONTINUE YOUR RESEARCH

Nearby tested output. Different details.

Within 25% of this minimum tested output rating. These are research candidates, not approved substitutes.

Vertiv
EXS 0040kTH16FN01000 ↗

Source record 2323916

40kW

Minimum tested active output

Reported input voltage380-415 VModularNo
○ ENERGY STAR feed
Liebert
EXS 0040kTH16FN01000 ↗

Source record 2323917

40kW

Minimum tested active output

Reported input voltage380-415 VModularNo
○ ENERGY STAR feed
Liebert
51SA160ARA ↗

Source record 2335934

40kW

Minimum tested active output

Reported input voltage480-480 VModularYes
○ ENERGY STAR feed