INDEPENDENT CRITICAL-POWER DIRECTORY Public sources. Clear decisions.
Liebert / SOURCE RECORD 4512357

56S(c3)(d5)J(f)N(h)(i)(j)

○ ENERGY STAR feedRetrieved 2026-09-12
THE CONFIGURATION BEHIND THESE RATINGS

Minimum tested model: 56S(c3)(d5)J(f)N(h)(i)(j)

The source identifies this model as the minimum tested configuration. The output ratings and load-specific efficiency values below apply to that configuration.

Efficiency test mode (lowest input dependency)
Voltage and Frequency Independent
Test input voltage
480 V
Test input frequency
60 Hz
Test output voltage
480 V
Test output frequency
60 Hz
60 kWMinimum tested active output
60 kVAMinimum tested apparent output
YesModular

These are source-reported minimum configuration ratings, not the maximum capacity of the model family. Test voltages above describe the efficiency test; reported voltage ranges below are separate source fields.

Inside the specification

SOURCE-REPORTED
Brand
Liebert
Catalog model identifier
56S(c3)(d5)J(f)N(h)(i)(j)
Reported input voltage
480-480 V
Reported output voltage
480-480 V
Reported input frequency
60-60 Hz
Topology
Multi-Mode Double Conversion
Modular design
Yes
Rack mountable
No
Application
Data Center,Consumer,Commercial
Reported markets
United States, Canada
Certification date
2025-10-16

Efficiency at a glance

Summary value reported by the source: 97.2%. Compare the tested model, voltage and mode above before interpreting differences.

25% of minimum tested output97%
50% of minimum tested output97.3%
75% of minimum tested output97.1%
100% of minimum tested output96.9%

Load-specific values: minimum configuration, lowest-input-dependency test mode. Unreported values remain blank in exports.

Other source records with this catalog model

The source publishes multiple records under this brand and model name. Keep the record ID and test conditions with your comparison; matching names do not establish interchangeable equipment.

CONTINUE YOUR RESEARCH

Nearby tested output. Different details.

Within 25% of this minimum tested output rating. These are research candidates, not approved substitutes.

Vertiv
EXS 0060kTK16FN01000 ↗

Source record 2325104

60kW

Minimum tested active output

Reported input voltage380-415 VModularNo
○ ENERGY STAR feed
Liebert
EXS 0060kTK16FN01000 ↗

Source record 2325105

60kW

Minimum tested active output

Reported input voltage380-415 VModularNo
○ ENERGY STAR feed
Schneider Electric
GVSUPS60KGS ↗

Source record 2325818

60kW

Minimum tested active output

Reported input voltage480-480 VModularNo