INDEPENDENT CRITICAL-POWER DIRECTORY Public sources. Clear decisions.
Schneider Electric / SOURCE RECORD 2333991

GVMRB180KG65S

○ ENERGY STAR feedRetrieved 2026-09-12
THE CONFIGURATION BEHIND THESE RATINGS

Minimum tested model: GVMPB180KGS

The catalog model is GVMRB180KG65S; the source identifies GVMPB180KGS as its minimum tested model. The output ratings and load-specific efficiency values below belong to that tested configuration.

Efficiency test mode (lowest input dependency)
Voltage and Frequency Independent
Test input voltage
480 V
Test input frequency
60 Hz
Test output voltage
480 V
Test output frequency
60 Hz
162 kWMinimum tested active output
180 kVAMinimum tested apparent output
NoModular

These are source-reported minimum configuration ratings, not the maximum capacity of the model family. Test voltages above describe the efficiency test; reported voltage ranges below are separate source fields.

Inside the specification

SOURCE-REPORTED
Brand
Schneider Electric
Catalog model identifier
GVMRB180KG65S
Reported input voltage
480-480 V
Reported output voltage
480-480 V
Reported input frequency
50-60 Hz
Topology
Double Conversion
Modular design
No
Rack mountable
No
Application
Data Center
Reported markets
United States, Canada
Certification date
2019-02-26

Efficiency at a glance

Summary value reported by the source: 96.9%. Compare the tested model, voltage and mode above before interpreting differences.

25% of minimum tested output95.6%
50% of minimum tested output96.4%
75% of minimum tested output96.6%
100% of minimum tested output96.4%

Load-specific values: minimum configuration, lowest-input-dependency test mode. Unreported values remain blank in exports.

CONTINUE YOUR RESEARCH

Nearby tested output. Different details.

Within 25% of this minimum tested output rating. These are research candidates, not approved substitutes.

Schneider Electric
GVMPB180KG65S ↗

Source record 2333989

162kW

Minimum tested active output
Tested model: GVMPB180KGS

Reported input voltage480-480 VModularNo
○ ENERGY STAR feed
Schneider Electric
GVMSB180KG65S ↗

Source record 2333990

162kW

Minimum tested active output
Tested model: GVMPB180KGS

Reported input voltage480-480 VModularNo
○ ENERGY STAR feed
Liebert
eXM 0160kTK16FN01000 ↗

Source record 2336443

160kW

Minimum tested active output

Reported input voltage228-478 VModularNo