INDEPENDENT CRITICAL-POWER DIRECTORY Public sources. Clear decisions.
Vertiv / SOURCE RECORD 2335266

53[S|P]30[H|Z][C|Y][0|E|F][0|B|E|F|H|J|K|L|M|N|P|R][0-8|A-E][0-9|A-Z][0-9|A-Z][0-9|A-Z][0-9|A-Z] [0-9|A-Z]

○ ENERGY STAR feedRetrieved 2026-09-12
THE CONFIGURATION BEHIND THESE RATINGS

Minimum tested model: 53S30HC00000000

The catalog model is 53[S|P]30[H|Z][C|Y][0|E|F][0|B|E|F|H|J|K|L|M|N|P|R][0-8|A-E][0-9|A-Z][0-9|A-Z][0-9|A-Z][0-9|A-Z] [0-9|A-Z]; the source identifies 53S30HC00000000 as its minimum tested model. The output ratings and load-specific efficiency values below belong to that tested configuration.

Efficiency test mode (lowest input dependency)
Voltage and Frequency Independent
Test input voltage
208 V
Test input frequency
60 Hz
Test output voltage
208 V
Test output frequency
60 Hz
30 kWMinimum tested active output
30 kVAMinimum tested apparent output
NoModular

These are source-reported minimum configuration ratings, not the maximum capacity of the model family. Test voltages above describe the efficiency test; reported voltage ranges below are separate source fields.

Inside the specification

SOURCE-REPORTED
Brand
Vertiv
Catalog model identifier
53[S|P]30[H|Z][C|Y][0|E|F][0|B|E|F|H|J|K|L|M|N|P|R][0-8|A-E][0-9|A-Z][0-9|A-Z][0-9|A-Z][0-9|A-Z] [0-9|A-Z]
Reported input voltage
208-220 V
Reported output voltage
208-220 V
Reported input frequency
60-60 Hz
Topology
Multi-Mode Double Conversion
Modular design
No
Rack mountable
No
Application
Commercial,Consumer,Data Center
Reported markets
United States, Taiwan, Japan, Canada
Certification date
2019-01-23

Efficiency at a glance

Summary value reported by the source: 94.8%. Compare the tested model, voltage and mode above before interpreting differences.

25% of minimum tested output92.4%
50% of minimum tested output94.1%
75% of minimum tested output93.9%
100% of minimum tested output93.4%

Load-specific values: minimum configuration, lowest-input-dependency test mode. Unreported values remain blank in exports.

CONTINUE YOUR RESEARCH

Nearby tested output. Different details.

Within 25% of this minimum tested output rating. These are research candidates, not approved substitutes.

Liebert
51SA030QAA ↗

Source record 2335932

30kW

Minimum tested active output

Reported input voltage480-480 VModularYes
○ ENERGY STAR feed
Vertiv
51SA030QAA ↗

Source record 2335933

30kW

Minimum tested active output

Reported input voltage480-480 VModularYes
○ ENERGY STAR feed