THE CONFIGURATION BEHIND THESE RATINGS

Minimum tested model: eXM 0200kTK16FN01000;

The catalog model is eXM 0200kTK16FN01000; the source identifies eXM 0200kTK16FN01000; as its minimum tested model. The output ratings and load-specific efficiency values below belong to that tested configuration.

Efficiency test mode (lowest input dependency)
Voltage and Frequency Independent
Test input voltage
415 V
Test input frequency
60 Hz
Test output voltage
415 V
Test output frequency
60 Hz
200 kWMinimum tested active output
200 kVAMinimum tested apparent output
NoModular

These are source-reported minimum configuration ratings, not the maximum capacity of the model family. Test voltages above describe the efficiency test; reported voltage ranges below are separate source fields.

Inside the specification

SOURCE-REPORTED
Brand
Vertiv
Catalog model identifier
eXM 0200kTK16FN01000
Reported input voltage
228-478 V
Reported output voltage
380-415 V
Reported input frequency
40-70 Hz
Topology
Multi-Mode Double Conversion
Modular design
No
Rack mountable
No
Application
Commercial,Consumer,Data Center
Reported markets
United States, Taiwan, Japan, Canada
Certification date
2019-01-23

Efficiency at a glance

Summary value reported by the source: 96.1%. Compare the tested model, voltage and mode above before interpreting differences.

25% of minimum tested output95.8%
50% of minimum tested output96.4%
75% of minimum tested output96.1%
100% of minimum tested output95.7%

Load-specific values: minimum configuration, lowest-input-dependency test mode. Unreported values remain blank in exports.

CONTINUE YOUR RESEARCH

Nearby tested output. Different details.

Within 25% of this minimum tested output rating. These are research candidates, not approved substitutes.

Liebert
51SA200LAA ↗

Source record 2335466

200kW

Minimum tested active output

Reported input voltage480-480 VModularYes
○ ENERGY STAR feed
Vertiv
51SA200LAA ↗

Source record 2335467

200kW

Minimum tested active output

Reported input voltage480-480 VModularYes
○ ENERGY STAR feed
Liebert
eXM 0200kTK16FN01000 ↗

Source record 2336441

200kW

Minimum tested active output
Tested model: eXM 0200kTK16FN01000;

Reported input voltage228-478 VModularNo
○ ENERGY STAR feed